Pepperl-fuchs Explosion Protection Fieldbus Segment Protector F2-SP-IC10.0.04.04.00 Part no:238250-0012
Fieldbus Segment Protector F2-SP-IC*
4 ... 10 outputs Ex ic (FISCO or Entity)
Advanced fault isolation at the spur
Segment Protector in Zone 2
Instruments in Zone 2 or Zone 1
For FOUNDATION Fieldbus H1 and PROFIBUS PA
Advanced Diagnostics at the spur
Power, Com, Terminator, Diagnostics, and Error LEDs
Function: F2-SP-IC*
The F2 Segment Protector with integrated diagnostics, a device coupler in aluminum housing, connects 4 ... 10 instruments to the segment with intrinsic safety (Ex ic, Zone 2). Device connections in Zone 1 require additional methods of ignition protection. Pre-engineering options are: cable glands in various materials; a choice of fixed or plug-in terminals with screw or spring-clamp connections. Short circuit, jabber, and bounce protection isolate most fault condition types from the segment.
The short circuit current limitation is adjustable for maximum load with Ex ic for gas groups IIB and IIC. The shield can be connected hard-to-ground or floating. A terminator with LED indication is selectable via jumper.
Short circuit protection ensures proper operation of the segment in case of unwanted faults at the spur. Intrinsic safety at the spur enables work on devices with hot work permit. The integrated fieldbus terminator features a high-availability design and can be chosen via a jumper.